Building Type: Residential Home
Primary Complaint: Water and Mold Damage
Project Number: 104022
Relevant Project Info:
Weather
- Sunny and mild
- Relative Humidity: 41% @ 54 Deg F
- CO2: 410 ppm CO: 1 ppm
- Home had been empty for several weeks prior to inspection being conducted.
Furnace / HVAC
- Electric Baseboards throughout
Recommendations
- Recommend replacing electric baseboard heaters with wall mounted, fan forced electric heaters. This will promote additional air circulation throughout the home and may also reduce heating costs.
Kitchen
- Water and mold damage noted under kitchen sink. Cabinet floor has been heavily damaged due to water and should be replaced.
- Ventilation fan over kitchen stove is set to recirculate air only and is not connected to the exterior of the home.
- RH: 42% Temp: 62 deg F. CO2 = 465 ppm CO = 0 ppm
Recommendations
- Recommend removal of water damaged materials.
Bedroom
- No areas of visible mold growth or elevated moisture levels.
- RH: 52% Temp: 58 deg F. CO2 = 474 ppm CO = 0 ppm
Recommendations
- Recommend replacing baseboard heater with an in-wall fan forced electric heater.
- Sink basin is improperly fastened to the underside of the vanity counter top. This may allow water to drip under the sink and cause damage to the cabinet.
- Significant water damage noted under vanity sink. This may be due to the improperly set sink basin. Floor of cabinet is heavily damaged and needs replacement.
- Sealant around bottom edge of shower surround appears in poor condition and should be replaced.
- Bath fittings on shower are loose and could allow water behind the shower surround.
- Ventilation fan in bathroom is present but is noisy and inefficient at removing relative humidity from inside the building.
- RH: 52% Temp: 58 deg F. CO2 = 498 ppm CO = 0 ppm
Recommendations
- Recommend removal / replacement of bathroom vanity.
- Recommend replacing all sealant around base of shower surround.
- Secure bath fittings to ensure moisture does not enter behind shower surround.
- Recommend installing a Panasonic Whisper Green® ventilation fan in bathroom to assist in evacuating the relative humidity from inside the building. Whisper Green ventilation fans operate consistently at a low volume (30 cfm) and automatically ramp up to a higher volume (80 cfm) when a motion sensor is activated. An integrated timer will maintain the higher volume for a set period of time and then return the fan to the lower operating level until activated again.
Master Bath
- Major water stains noted on linoleum flooring throughout bathroom.
- Elevated moisture levels were noted in the areas where linoleum stains were found.
- Shower door appears to be leaking and allowing moisture to accumulate on the floor.
- Wax seal around the base of toilet has likely failed due to elevated moisture levels around the toilet base.
- Tiles around shower enclosure are heavily damaged.
- Elevated moisture levels were noted behind shower tiles.
- No ventilation fan present in bathroom.
- Heavy rust deposits present on metal objects (light fixtures, drywall corners etc…) Rust is likely due to high levels of relative humidity due to no ventilation fan in bathroom.
- Minor staining present behind master vanity. No elevated moisture levels noted.
- RH: 51% Temp: 57 deg F. CO2 = 474 ppm CO = 0 ppm
- Recommend removal of entire shower surround due to heavy damage.
- Recommend pulling up linoleum floor to address elevated moisture levels and install new flooring.
- Recommend replacing wax seal around base of toilet.
- Recommend installing a Panasonic Whisper Green® ventilation fan in bathroom to assist in evacuating the relative humidity from inside the building. Whisper Green ventilation fans operate consistently at a low volume (30 cfm) and automatically ramp up to a higher volume (80 cfm) when a motion sensor is activated. An integrated timer will maintain the higher volume for a set period of time and then return the fan to the lower operating level until activated again.
- Recommend replacing all light fixtures due to corrosion.
Exterior
- Significant amount of water staining found on exterior siding on the back side of the condo unit.
- No elevated moisture levels were measured in stained siding. This may indicate a previous water intrusion incident from the unit above that has since been repaired.
- Evidence of foundation work being conducted under building. Work of this nature should not affect the interior of the building.
- Decking appears in good shape with no areas of rot noted.
Recommendations
- Recommend monitoring rear siding of home to ensure water staining does not get any worse. If client notices a significant increase to the staining, a more thorough inspection may be needed in the unit above.




